CDV-582, CDH-582, CDS-582
Encoder, safety-related according to DIN EN 61508: up to SIL CL3 or DIN EN ISO 13849: up to PLe
Double Scanning Unit
Interface: PROFINET / PROFIsafe
Optional additional interfaces: SSI, Incremental, external Preset inputs


***************************************************************************************************
*       I N S T R U C T I O N S  F O R  T H E  D E V I C E  F I R M W A R E  V E R S I O N        *
***************************************************************************************************
Currently, there are two device firmware versions: 1.xx and 2.xx.
The name plate (printed at the bottom right) indicates which firmware version the specific
device supports:
  - 1.xx: No imprint, or imprint "V001"
  - 2.xx: Imprint "V002"
The user manual indicates functional enhancements that require device firmware version 2.xx
Devices with firmware version 1.xx can be operated with GSDML files for firmware versions
1.xx or 2.xx, but the function extensions under firmware version 2.xx cannot be used
and must not be configured in the controller.
Non-firmware-compatible configurations will prevent the device from starting up!

***************************************************************************************************



*********************************** FOR FIRMWARE VERSION 1.xx/2.xx ***********************************

SIEMENS TIA-Portal and other automation systems:
XML file: GSDML-V2.44-TR-0153-CD_582_-EPN-xxxxxxxx.xml, GSDML version V2.44
New features, for example: PROFINET Security Class 1, PROFIsafe Address type 2, System Redundancy S2 ...
Bitmap file: GSDML-0153-0404-CD_582_-EPN.bmp

SIEMENS SIMATIC Manager and other automation systems (16 bit register):
XML file: GSDML-V2.3-TR-0153-CD_582_-EPN-xxxxxxxx.xml, GSDM version V2.3
Bitmap file: GSDML-0153-0404-CD_582_-EPN.bmp

As from SIEMENS TIA-Portal V19 and other automation systems,
which support the GSDX container format with digital signature:
XML file: GSDX-V1.0-TR-CD_582_-EPN-xxxxxxxx-133718.gsdx
Bitmap file: GSDML-0153-0404-CD_582_-EPN.bmp

ABB AC500-S PM583/SM560 Control systems
XML file: GSDML-V2.44-TR-0153-CD_582_-EPN-ABB-xxxxxxxx.xml, GSDML version V2.44
New features, for example: PROFINET Security Class 1, PROFIsafe Address type 2, System Redundancy S2 ...
Bitmap file: GSDML-0153-0404-CD_582_-EPN-ABB.bmp

*********************************** FOR FIRMWARE VERSION 1.xx/2.xx ***********************************



************************************* FOR FIRMWARE VERSION 1.xx *************************************

Sub folder ...\Firmware 1.xx

SIEMENS TIA-Portal and other automation systems:
XML file: GSDML-V2.34-TR-0153-CD_582_-EPN-xxxxxxxx.xml, GSDML version V2.34
Bitmap file: GSDML-0153-0404-CD_582_-EPN.bmp

ABB AC500-S PM583/SM560 Control systems
XML file: GSDML-V2.34-TR-0153-CD_582_-EPN-ABB-xxxxxxxx.xml, GSDML version V2.34
Bitmap file: GSDML-0153-0404-CD_582_-EPN-ABB.bmp

************************************* FOR FIRMWARE VERSION 1.xx *************************************



DOCUMENTATION:

Safety manual
www.tr-electronic.de/f/TR-ECE-BA-D-0142  (german)
www.tr-electronic.de/f/TR-ECE-BA-GB-0142 (english)

User manual
www.tr-electronic.de/f/TR-ECE-BA-D-0139  (german)
www.tr-electronic.de/f/TR-ECE-BA-GB-0139 (english)